Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability | 1000 units / year |
Delivery Time | 45 days |
Packaging Details | Standard export package |
Rated Voltage | 110/126kV |
Rated Current | 3150A 40kA |
Frequency | 50/60Hz |
Insulation Gas | SF6 |
Brand Name | Tianan Electric |
Model Number | LW39-126 |
Certification | XIHARI |
Place of Origin | CHINA |
View Detail Information
Explore similar products
110kV Live Tank Outdoor High Voltage Circuit Breaker / Vacuum Circuit Breaker
Outdoor HV Porcelain Stanchion Type Vacuum Circuit Breaker Filled With SF6
Indoor High Voltage Vacuum Circuit Breaker / Hv Circuit Breaker VS1-12 Series
Outdoor SF6 High Voltage Circuit Breaker AC 50Hz For Measurement And Protection
Product Specification
Payment Terms | L/C, D/A, D/P, T/T, Western Union, MoneyGram | Supply Ability | 1000 units / year |
Delivery Time | 45 days | Packaging Details | Standard export package |
Rated Voltage | 110/126kV | Rated Current | 3150A 40kA |
Frequency | 50/60Hz | Insulation Gas | SF6 |
Brand Name | Tianan Electric | Model Number | LW39-126 |
Certification | XIHARI | Place of Origin | CHINA |
High Light | high voltage vacuum circuit breaker ,hv circuit breaker |
110kV 126kV High Voltage Circuit Breaker 3150A - 40kA Sf6 Circuit Breaker
Product Description
LW39-126 type circuit breaker is a high performance new type HV SF6 circuit breaker. Based on sufficient absorbing and digesting advanced technology of foreign SF6 circuit breaker and requirement of national standard, It combining domestic commercial manufacture level and design. This product is used in electric system with 50Hz, 110kV system nominal voltage, which is main electrical equipment controlled and protected by power station and substation.
Serial No. | Name | Unit | Value |
1 | Ambient temperature | ºC | -50ºC-40ºC |
2 | Rated voltage | KV | 126 |
3 | Rated power frequency withstand voltage (1min) | ||
3.1 | To earth | kV | 230 |
3.2 | Across open contact | kV | 230+73 |
4 | Rated lightning impulse withstand voltage | ||
4.1 | To earth | kV | 550 |
4.2 | Across open contact | kV | 550+103 |
5 | Rated frequency | Hz | 50 |
6 | Rated value | A | 3150 |
7 | First pole to clear factor | 1.5 | |
8 | Rated short-circuit breakering current (Isc) | kA | 40 |
9 | Rated short-circuit making current (peak) | kA | 100/104 |
10 | Rated hsort-time withstand current | kA | 40 |
11 | Rated peak withstand current | kA | 100/104 |
12 | Rated duration of short-circuit | s | 4 |
13 | Rated out of phase breaking current | kA | 10 |
14 | Short-line fault breaking current | kA | 90%Isc,75Isc |
15 | Rated line charging breaking current | A | 31.5 |
16 | Rated operating sequence | o-0.3s-CO-180s-CO | |
17 | Resistance of main contact | μΩ | ≤35 |
18 | Rated SF6 gas pressure (20ºC gauge pressure) | Mpa | 0.6 (or SF6+CF4) 50Hz |
19 | Alarm/ minimum functional pressure (20ºC gauge pressure) | Mpa | 0.55/0.50 50Hz |
20 | Annual leakage of SF6 gas | % | ≤0.5 |
21 | Gas humidity content (L/L) (20ºC at handover) | L/L | ≤150x10-6 |
22 | Mechanical endurance | Times | 10000 |
23 | Radio interference level | mv | ≤500 |
24 | Creepage distance | mm | 3906 |
25 | Weight of SF6 gas filled for each CB | kg | 8 |
26 | Weight of one set of CB | kg | 1700 |
Major Technical parameters of mechanism
No. | Name | Unit | Data | ||
1 | Energy-store motor | Normal voltage rang | V | 85%--- 110% | |
Rated voltage | DC220/AC220 | ||||
Rated power | W | 720 | |||
2 | Storage time (at rated voltage) | s | ≤20 | ||
3 | Rated voltage/current of opening coil | V/A | DC110V/4A, DC220V/2A | ||
AC220V/5A | |||||
4 | Auxiliary Switch | Rated current | A | 3(DC220V)/5 (DC110V) | |
Number of auxiliary contacts: normally opened/closed | Pair | 11/11 | |||
5 | Trip switch | Rated current | A | 3(DC220V)/5 (DC110V) | |
Number of auxiliary contacts: normally opened/closed | Pair | 2/2 | |||
6 | Capacity of terminal carry continuous current | A | 10 | ||
7 | Voltage of heater and lighting circuit | V | AC220 | ||
8 | Mechanical endurance | Times | 10000 | ||
Company Details
Business Type:
Manufacturer,Exporter,Trading Company,Seller
Year Established:
1969
Total Annual:
250000000-300000000
Employee Number:
3000~3500
Ecer Certification:
Verified Supplier
Ningbo Tianan (Group) Co, Ltd is a famous leading influential enterprise of the power transmission equipment manufacturing in China.It was founded in 1969,currently under the group, we have 1 national-level R&D center, 2 provincial-level R&D center, 10 professional companies, 70 sales office... Ningbo Tianan (Group) Co, Ltd is a famous leading influential enterprise of the power transmission equipment manufacturing in China.It was founded in 1969,currently under the group, we have 1 national-level R&D center, 2 provincial-level R&D center, 10 professional companies, 70 sales office...
Get in touch with us
Leave a Message, we will call you back quickly!