Payment Terms | T/T |
Supply Ability | 10units/month |
Delivery Time | 10 work days |
Packaging Details | Export standard wooden case with fumigation free |
Usage | Capacitance & Tan Delta Tester within 12KV or 12KV |
HV output | 0-12KV |
Test object | Motor , power generator and so on. |
Test range | 50pF~1uF; 0~12KV |
Anti-interference | Variable Frequency Method, 5mA |
Test Accuracy | Reading*1.5% |
Brand Name | Fanke High-Voltage |
Model Number | FKGST 12KV |
Certification | ISO9001 |
Place of Origin | China |
View Detail Information
Explore similar products
Non Contact Tachometer Generator Test Equipment For Rotating Speed Testing
12KV Transformer Capacitance & Tan Delta Test Set Automatic 0-12KV HV Output
Large Power Generator Test Equipment Power Frequency Resonant Circuit Test
Portable Motor Rotation Indicator / Three Phase Power Phase Sequence Tester
Product Specification
Payment Terms | T/T | Supply Ability | 10units/month |
Delivery Time | 10 work days | Packaging Details | Export standard wooden case with fumigation free |
Usage | Capacitance & Tan Delta Tester within 12KV or 12KV | HV output | 0-12KV |
Test object | Motor , power generator and so on. | Test range | 50pF~1uF; 0~12KV |
Anti-interference | Variable Frequency Method, 5mA | Test Accuracy | Reading*1.5% |
Brand Name | Fanke High-Voltage | Model Number | FKGST 12KV |
Certification | ISO9001 | Place of Origin | China |
High Light | high voltage insulation tester ,high voltage testing machine |
12KV Transformer Capacitance & Tan Delta Tester , Automatic Tan Delta Tester , Generator Tan Delta Tester
I. Products Description
FKGST 12KV Tan Delta (dissipation factor) Tester consists of variable frequency power, tan delta bridge, testing transformer and standard capacitor inside the tester. Variable frequency power can produce five kinds of frequency: 45Hz, 50Hz, 55Hz, 60Hz and 65Hz under which test can be done. Variable frequency technique adopted in this tester can ensure high accuracy in high interference environment.
Model FKGST Automatic 12KV Capacitance &Dissipation Factor Test Set is used to measure dissipation factor (PF) in heavy interference site such as power plants or power substations. It can also be used in laboratory for high accurate test. The meter is whole in one designed: including precision digital bridge, power unit, reference capacitor (CN), step-up transformer and other electronic circuits. It’s also using frequency shift technology, FFT (Fast Fourier Transform algorithm) and digital filtering. When started, it’s running automatically and then outputs the results on LCD display and prints the results automatically.
II. Test principle
Fig 1 Wiring Diagram of Main Power
RX1---Sampling resistance in ungrounded test specimen measurement
RX2---Sampling resistance in grounded test specimen measurement
CN---Standard capacitor
RN---Sampling resistance of reference signal
CVT---Voltage output terminal in CVT measurement by means of self-excitation.
III. Technical Parameters
1. Input: 220V+5%, 50Hz, 1KVA
2. Output:voltage:0~12kV (0.5kV/step to raise voltage)
current:100mA continuous
Max. 200mA, 5min on/15min off (10kV)
Max.160mA, 5min on/15min off (12kV)
3.Test range:
3.1 voltage:0~12kV resolution:1V
3.2 capacitance: 10kV, 50pF~60000pF(50Hz)
12kV, 50pF~44000pF(50Hz)
0.5kV, 50pF~1uF(50Hz)
3.3 Max. resolution:0.01pF
3.4 Tan delta:0~10% Maximum resolution:0.00001
4.Accuracy:
4.1 voltage(RMS):+200V
4.2 capacitance:+(Reading*1.0%+1pF)
4.3 in ungrounded test specimen measurement +Reading*1.5%+1pF
4.4 in grounded test specimen measurement tan delta:+reading*1.0%+0.0005
5.Operational environment:
5.1operation temperature:-5℃~55℃
5.2 humidity:<85%
5.3 storage temperature:-20℃~55℃
III. Configuration:
SN | NAME | Qty |
1 | FKGST Automatic 12KV Capacitance &Dissipation Factor Tester | 1set |
2 | 10 meters Hipot measuring signal lines (red) | 1pec |
3 | 10 meters measuring signal lines (black) | 2pecs |
4 | 8 m CVT Low voltage output line | 1pec |
5 | Power line | 1pec |
6 | 8 m Earth line | 1pec |
7 | Spare printing paper | 1pec |
8 | 5A fuse | 1pec |
9 | Feltpad | 1pec |
10 | Manual | 1pec |
11 | certificate of inspection | 1pec |
12 | accessory case fro connection lines | 1pec |
Company Details
Business Type:
Manufacturer,Exporter,Seller
Year Established:
2003
Total Annual:
6000000-10000000
Employee Number:
100~120
Ecer Certification:
Active Member
Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa... Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa...
Get in touch with us
Leave a Message, we will call you back quickly!