Payment Terms | T/T |
Supply Ability | 20 sets / month |
Delivery Time | 15-20working days |
Packaging Details | Export standard wooden case with fumigation free |
Usage | CT PT calibarting test |
Test object range | S level CT And 100/3 PT Calibating test |
CT/PT range | Current :(1%-149%)In (In =5A) (5%-149%)In (In =1A) Voltage:(5%-149%)Un (Un =100V,150V,100V/3) ; (5%-149%)Un (Un =100V/3) |
Test output range | In-phase component (%): 0.0001~200.0 Resolution: 0.0001 Quadrature component: 0.001~700.0 Resolution: 0.001 Impedance(Ω): 0.0001~20.0 Resolution: 0.0001 Admittance (ms): 0.0001~20.0 Resolution: 0.0001 |
Elementary error | In-phase component:ΔX=±(X×2%+Y×2%)±Dx Quadrature component:ΔY=±(X×2%+Y×2%×34.48)±Dy |
Power Supply | 220V , 50Hz |
Brand Name | Fanke High-voltage |
Model Number | HGQB-C series |
Certification | ISO9001 |
Place of Origin | Wuhan ,China |
View Detail Information
Explore similar products
SF6 Gas Insulation Inflatable Experimental High Voltage Transformer
SF6 Gas Insulation Inflatable Experimental High Voltage Transformer
2000A~5000A CT PT Testing Equipment Secondary Current Injection Test Kit One
150Hz CT PT Testing Equipment Three Times Frequency Power Generator
Product Specification
Payment Terms | T/T | Supply Ability | 20 sets / month |
Delivery Time | 15-20working days | Packaging Details | Export standard wooden case with fumigation free |
Usage | CT PT calibarting test | Test object range | S level CT And 100/3 PT Calibating test |
CT/PT range | Current :(1%-149%)In (In =5A) (5%-149%)In (In =1A) Voltage:(5%-149%)Un (Un =100V,150V,100V/3) ; (5%-149%)Un (Un =100V/3) | Test output range | In-phase component (%): 0.0001~200.0 Resolution: 0.0001 Quadrature component: 0.001~700.0 Resolution: 0.001 Impedance(Ω): 0.0001~20.0 Resolution: 0.0001 Admittance (ms): 0.0001~20.0 Resolution: 0.0001 |
Elementary error | In-phase component:ΔX=±(X×2%+Y×2%)±Dx Quadrature component:ΔY=±(X×2%+Y×2%×34.48)±Dy | Power Supply | 220V , 50Hz |
Brand Name | Fanke High-voltage | Model Number | HGQB-C series |
Certification | ISO9001 | Place of Origin | Wuhan ,China |
High Light | ct pt analyzer ,ct pt test set |
CT PT On-Site Calibration Test Set , CT/PT Calibrator , S level CT And 100/3 PT Calibating
I. Product Description:
The HGQB-C CT/PT calibrating test set is a novel automatic test systems. It uses advanced electronic technology to directly collect and decompose the error signals of the CT/PT, and after proper calculation, then the percentage points, phase errors and orthogonal errors of the tested CT/PT are displayed in digital LCD at the same time.
The calibrating set is special for calibrating test to S-level CT and PT with secondary voltage of 100/3V. It can be used in the laboratory or in the field. This test set is widely used in metrology, power supply and other departments and transformer manufacturers. It is an ideal instrument for testing and verifying Transformers.
II. Application filed
III. Components list of the test set
SN | Name | Model | Technical parameters | Unit |
1 | Mutual inductor calibrator | HGQB-C | 2.0-grade | 1 set |
2 | CT load bank | FY96 |
Rated current:5A Capacitance:2.5VA-80VA |
1 set |
3 | PT load bank | FY95 | Rated voltage:100V Capacitance:1.25VA-158.75VA | 1 set |
4 | CT | HL-S23S | Current:5A-1000A/5A,Grade:0.05S | 1 set |
5 | PT | HJ-S10G3 | Ratio:10KV/100V, Grade:0.05 | 1 set |
6 | voltage regulating Control cabinet | KZX05-HII | 5KVA+300VA | 1 set |
7 | Current lead |
1000A*3m*1 piece 500A*3m*2 pieces 250A*3m*2 pieces 100A*3m*2 pieces |
1 set | |
8 | Current line, pressure-wire | 1 set | ||
9 | Software | 1 set |
V. Technical data of the test set
Ambient conditions |
T: 5℃--40℃ RH:<80%(25℃) Altitude:<2500m Supply frequency: 50 Hz±0.5 Hz Power voltage: 220V±5V |
Measuring range |
In-phase component (%): 0.0001~200.0 Resolution: 0.0001 Quadrature component: 0.001~700.0 Resolution: 0.001 Impedance(Ω): 0.0001~20.0 Resolution: 0.0001 Admittance (ms): 0.0001~20.0 Resolution: 0.0001 |
Elementary error |
In-phase component:ΔX=±(X×2%+Y×2%)±Dx Quadrature component:ΔY=±(X×2%+Y×2%×34.48)±Dy “X”,“Y”——Displayed value “Dx,Dy”——Quantization error Dx=2,Dy=5 Dial-gage: 2-grade |
Working range |
Current :(1%-149%)In (In =5A) (5%-149%)In (In =1A) Voltage:(5%-149%)Un (Un =100V,150V,100V/3) (5%-149%)Un (Un =100V/3) |
Dimension(mm) | 260 mm(L)×350 mm (W)×150 mm(H) |
Weight(Kg) | 6 Kg |
Company Details
Business Type:
Manufacturer,Exporter,Seller
Year Established:
2003
Total Annual:
6000000-10000000
Employee Number:
100~120
Ecer Certification:
Active Member
Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa... Founded in 2003, FANKE is the domestic leader specializing in designing and manufacturing HV test, measurement and overhaul equipments. In 2003, Wuhan HIGHVOLT Co.,Ltd is established as our subsidiary. We provide a diversity of complete testing solutions and one-stop service for electric power compa...
Get in touch with us
Leave a Message, we will call you back quickly!