Payment Terms | T/T, Western Union |
Supply Ability | 1000 PCS/month |
Delivery Time | 30~35 days |
Packaging Details | Plywood case |
COP | 4~5 |
Compressor | Screw |
Supply power | 380V 3N~50Hz |
Refrigerant | R410A, R22, R407C |
Warranty | 1 Year |
Installation | Freestanding |
Hot water temperature | 55~60° C |
Heating capacity range | 88~280kW |
Brand Name | Shenglin |
Model Number | GSHP series |
Certification | CE |
Place of Origin | China |
View Detail Information
Explore similar products
3.2kw Swimming Pool Inverter Heat Pump , Low Temperature Heat Pump DN25
Dn25 15kw Air Source Heat Pumps For Swimming Pool Hotel Villa
300l Circle Split Heater 7.5kW Air Source Heat Pumps Freestanding
BFFR Ultra Low 3.6COP Air Source Heat Pumps Copeland EVI Central Air Heat Pump
Product Specification
Payment Terms | T/T, Western Union | Supply Ability | 1000 PCS/month |
Delivery Time | 30~35 days | Packaging Details | Plywood case |
COP | 4~5 | Compressor | Screw |
Supply power | 380V 3N~50Hz | Refrigerant | R410A, R22, R407C |
Warranty | 1 Year | Installation | Freestanding |
Hot water temperature | 55~60° C | Heating capacity range | 88~280kW |
Brand Name | Shenglin | Model Number | GSHP series |
Certification | CE | Place of Origin | China |
High Light | 50HP Water Source Heat Pumps ,280kW Water Source Heat Pumps ,280kW Water Source modular heat pump |
Modular Water Source Heat Pump Unit
● Energy-saving and reliable: Multi-level energy adjustment easily solves the long-term practical problem of low cooling efficiency during partial load operation, which has plagued traditional chillers. Compared with ordinary units, the IPLV coefficient is increased by more than 15%. Each modular unit has unparalleled independence during modular installation. Each module unit is an independent and complete refrigeration system, which operates in an orderly manner under the control of a microcomputer with advanced fault self-diagnosis function. When any module fails, it will not affect the operation of other units.
● Easy installation: The handling work is divided into parts, easy and free. In modular installation, standard modular units can be assembled on site, saving installation and transportation costs by more than 30% compared with large-scale units with the same cooling capacity.
● Flexible expansion: The flexibility of free expansion during modular installation allows users and designers to have no worries. Modular and freely expandable features allow users to arrange purchase and installation in stages according to their own business development needs; especially large-scale projects or renovation projects constructed in stages can be invested in stages according to the capital status to increase capital utilization.
● Quiet operation: The use of low-noise fully enclosed scroll compressors has the industry-leading level of noise at night in the cooling mode; relying on the national precision noise room and noise spectrum analysis, the components are strictly compared, selected, and the structure is The professional noise reduction design has been carried out with the pipeline, and the noise of the unit has been significantly improved.
Technical paramater:
Unit model (GSHP) |
GSHP 80KA |
GSHP 120KA |
GSHP 160KA |
GSHP 200KA |
GSHP 260KA |
||
Cooling capacity | kW | 80 | 120 | 160 | 200 | 255 | |
Heating capacity | kW | 88 | 132 | 176 | 220 | 280 | |
Power using | 3Ph 380V 50Hz | ||||||
Refrigerant | R410A | ||||||
Energy regulation | % | 50,100 | 33,66,100 | 25,50,75,100 | 25,50,75,100 | 33,66,100 | |
Compressor | Cooling input power | kW | 14.5 | 21.8 | 29 | 36.3 | 45.6 |
Heating input power | kW | 17.6 | 26.4 | 35.2 | 44 | 55.2 | |
Maximum operating current | A | 2x26 | 3x26 | 4x26 | 4x33 | 3x55 | |
Use side heat exchanger |
Water side resistance | kPa | 50 | 54 | 58 | 60 | 62 |
Pipe specifications | mm | DN50 | DN65 | DN80 | DN100 | DN100 | |
Cooling conditions use water side flow | m3 /h | 13.8 | 20.6 | 27.5 | 34.5 | 43.8 | |
Heating conditions heat side water flow | m3 /h | 7.6 | 11.4 | 15.1 | 19 | 24.2 | |
Heat side heat exchanger |
Water side resistance | kPa | 45 | 48 | 52 | 55 | 57 |
Water flow | mm | DN50 | DN65 | DN80 | DN100 | DN100 | |
Cooling conditions use water side flow | m3 /h | 7.4 | 24.4 | 14.8 | 18.5 | 23.5 | |
Heating conditions heat side water flow | m3 /h | 15.1 | 22.7 | 30.3 | 37.8 | 48.2 | |
Overall | Length | mm | 1700 | 2300 | 2500 | 2700 | 2800 |
Width | mm | 650 | 730 | 730 | 800 | 1000 | |
Height | mm | 1372 | 1500 | 1500 | 1500 | 1600 | |
Unit net weight | Kg | 650 | 800 | 1000 | 1200 | 1600 |
1) The cooling capacity of the unit and the power consumption calibration conditions of the compressor: evaporator inlet and outlet water temp (12/7°C), condenser inlet and outlet water temp(18/29°C)
2) Calibration conditions for heat generation and compressor power consumption: evaporator inlet and outlet water temp (15/8°C), condenser inlet and outlet water temp (40/45°C)
3) The standard pressure-bearing capacity of the condenser and evaporator water circuit is 1.0MPa, and the fouling factor: 0.086 ㎡°C/kW
4) If the specifications listed in this table change, please excuse for no notice
Note: Partial heat recovery type and full heat recovery type are optional.
Company Details
Business Type:
Manufacturer
Year Established:
2009
Employee Number:
>100
Ecer Certification:
Active Member
Introduction: Shanghai Shenglin is a professional manufacturer and sales of heat exchanger and air conditioning unit since 2009, located in Shanghai, China. Shanghai Shenglin was established in 2009, at the beginning only do HVAC international trading, then from 2012, we ... Introduction: Shanghai Shenglin is a professional manufacturer and sales of heat exchanger and air conditioning unit since 2009, located in Shanghai, China. Shanghai Shenglin was established in 2009, at the beginning only do HVAC international trading, then from 2012, we ...
Get in touch with us
Leave a Message, we will call you back quickly!